International Standard IEC 60038, IEC standard voltages, defines a set of standard nominal electricity supply voltages for low voltage and high voltage AC and DC systems.
Tables The standard primarily contains a set of tables, each of which define a set of standard nominal supply voltages that may be chosen from, as follows:
Table 1 defines those for AC systems where voltage is to be within the range 100 to 1000. Table 2 defines those for DC and AC traction systems, and provides DC options from 400 to 3600, and AC options from 4750 to 27500. Table 3 defines those for three-phase AC systems where voltage is to be within the range 1kV to 35kV. Table 4 defines those for three-phase AC systems where voltage is to be within the range 35kV to 230kV. Table 5 defines those for three-phase AC systems where voltage is to exceed 230kV, and gives options up to 1200kV. Table 6 defines nominal voltages for equipment below 120 V AC, or 750 V DC.
Low voltage systems (Table 1) Standard nominal voltages that can be used for low voltage systems in the 100-1000V range are as follows:
For three-phase 3 or 4-wire systems at 50 Hz: 230 V (3-wire) 230/400 V 400/690 V 1000 V (3-wire) For three-phase 3 or 4-wire systems at 60 Hz: 120/208 V 240 V (3-wire) 230/400 V 277/480 V 480 V (3-wire) 347/600 V 600 V (3-wire) For single-phase 3-wire systems at 60 Hz (American split-phase): 120/240 V Note that with the exception of the American split-phase case, where two voltages are given separated by a slash, these represent 4-wire cases; the first voltage corresponding to that between phase and neutral, and the second between phases. Single voltage values are for 3-wire cases and thus correspond to that between phases. In the case of American split-phase, the first value is that between a hot and the centre-tapped neutral, while the second is that between the pair of hots. All AC voltages are RMS. Three-phase 3-wire is without neutral, while three-phase 4-wire is with neutral. Of historical interest, it is noted that the 230/400 V three-phase option replaced the former 220/380 V and 240/415 V systems. Similarly the 380/660 V system was replaced with 400/690 V. Migration from these older voltage systems was required by amendment 1 to the 1983 edition of the standard, published in 1994. Those countries with a 220/380 V systems were required to bring their voltage within +6/-10% of 230/400 V, while those with a 240/415 V system were required to bring their voltage within +10/-6% of 230/400 V, as soon as possible, and no later than the year 2003, thus achieving all systems being within ±10% of 230/400 V by that deadline.
See also Mains electricity by country