ArticleslgStudy

physics

IEC 61000-4-5

IEC 61000-4-5 is a physics topic covered in the lgStudy science library. This page brings together a partial reference excerpt, illustrations, worked examples, real-world applications and a short study plan, so you can understand IEC 61000-4-5 rather than just read about it. In short: IEC 61000-4-5 is an international standard by the International Electrotechnical Commission on surge immunity. In an electrical installation, disruptive surges can appear on power and data lines.

IEC 61000-4-5 — main illustration
IEC 61000-4-5 — illustration

Key takeaways

  • IEC 61000-4-5 belongs to physics; place it in that map before memorising details.
  • Learn the definition first, then one example that makes the definition concrete.
  • Connect IEC 61000-4-5 to a quantity you can measure, compute or draw — that is where exam questions come from.
  • Reproduce the core statement of IEC 61000-4-5 from memory before moving on to harder problems.

Reference excerpt

IEC 61000-4-5 is an international standard by the International Electrotechnical Commission on surge immunity. In an electrical installation, disruptive surges can appear on power and data lines. Their sources include abrupt load switching and faults in the power system, as well as induced lightning transients from an indirect lightning strike (direct lightning is out of scope in this standard). It necessitates the test of surge immunity in electrical or electronic equipment. IEC 61000-4-5 defines test set-up, procedures, and classification levels. In particular, it standardizes the required surge voltage and current waveforms for laboratory testing, with the "1.2/50-8/20 μs" impulse being the most frequently used surge waveform. Although this standard is designed for testing equipment as a whole at system level, not for individual protection devices, in practice this surge waveform is often also used for rating Transient Voltage Suppressors (TVS), Gas Discharge Tubes (GDT), Metal Oxide Varistors (MOV), and other surge protection devices. The current version is Third Edition (2014), amended in 2017.

Test Setup Two major components are defined in this standard: two types of Combination Wave Generators (CWG) and various Coupling/Decoupling Networks (CDN) depending on the test level and type. First, a Combination Wave Generator is a standardized impulse generator (sometimes also referred to as a lightning surge generator), it's used for producing simulated, standard voltage and current surges under laboratory conditions. Subsequently, the surge is transmitted into a port of the Device-Under-Test (DUT) via a coupling network. Finally, to prevent surges from reaching other devices via the power system during the test, a decoupling network is also inserted between the power line and the DUT.

Surge Waveforms The Combination Wave Generator is required to have an output floating from ground, and be capable of generating both positive and negative impulses. Its repetition rate should be at least one impulse per 60 seconds. The surge is defined by the Combination Wave Generator's open-circuit voltage and short-circuit current waveforms, characterized by front time, duration, and peak values. With an open circuit output, the surge voltage is a double exponential pulse in the form of k ( e − α t − e − β t ) {\displaystyle k(e^{-\alpha t}-e^{-\beta t})} . With a short circuit output, the surge current waveform is a damped sine wave. The ratio between the peak open-circuit voltage and the peak short-circuit current is 2, giving an effective output impedance of 2 Ω.

Usually, the voltage waveform has a 1.2 μs front time and a 50 μs duration, and the current waveform has a 8 μs front time and 20 μs duration. This is the most commonly used surge waveform for most applications, often referred to as a "1.2/50-8/20 μs" surge. Alternatively, for outdoor telecommunication networks that experience a higher surge level, the standard also defines a more energetic generator with a 10/700 μs voltage waveform and a 5/320 μs current waveform. Front time and duration are not measured directly, but as virtual parameters derived from measurements. For open-circuit voltage, front time is defined to be 1.67 times the 30%-90% rise time, duration is defined as the time interval between the 50% point of its rising edge and the 50% point of its falling edge. For short-circuit current, front time is defined to be 1.25 times the 10%-90% rise time, duration is defined as 1.18 times time interval between the 50% point of its rising edge and the 50% point of its falling edge. At the output of the generator, a 30% undershoot below zero is allowed. There's no overshoot or overshoot limit at the output of the Coupling Network.

Comparison with different standards

IEC 60060-1 It's worth noting that both "1.2/50 μs" voltage and "8/20 μs" current impulses are classic waveforms with a well-established history of use in high-voltage testing for electric power transmission. Thus, these waveforms are also defined by IEC 60060-1 "High-Voltage Test Techniques" and other standards in this context. In fact, the waveform definitions in IEC 61000-4-5 were originally based on IEC 60060-1. Nevertheless, there are important differences. In traditional high-voltage testing, voltage and current impulses are tested separately, not in combination. The "1.2/50 μs" generator is designed for insulation testing, and produces a high-voltage, low-current impulse into a high-impedance load. The output current of this generator is on the milliampere scale. The "8/20 μs" generator is designed for surge arrester testing, and produces a high-current surge into a low-impedance load. On the other hand, modern electronic devices can be high and low-impedance loads simultaneously due to non-linear devices, protection circuits, and arcing in a dielectric breakdown. As a result, it motivated the creation of the Combination Wave Generator with the ability to generate a high-voltage, high-current output during the same surge. In addition, both standards have different waveform tolerances and other technical requirements. Thus, IEC 61000-4-5 is not to be confused with IEC 60060-1 and other high-voltage tests that also use a "1.2/50 μs" or "8/20 μs" impulse.

… excerpt ends here. Continue reading the full article.

Illustrations

IEC 61000-4-5 illustration
IEC 61000-4-5: Simplified Schematic of the 1.2/50-8/20 μs Combination Wave Generator
Simplified Schematic of the 1.2/50-8/20 μs Combination Wave Generator
IEC 61000-4-5: Simplified Schematic of the 10/700-5/320 μs Combination Wave Generator
Simplified Schematic of the 10/700-5/320 μs Combination Wave Generator

Worked examples

Example 1 — a first encounter with IEC 61000-4-5

Start with the simplest possible case. Write down what IEC 61000-4-5 claims or describes in one sentence, then invent the smallest concrete situation in which that sentence is true. In physics, the smallest case is usually a single object, a single equation or a single measurement. Check that every symbol or term in your sentence has a meaning in that case.

Example 2 — changing one variable

Take the situation from Example 1 and change exactly one quantity: double it, halve it, or set it to zero. Predict what should happen to IEC 61000-4-5 before you calculate. Comparing your prediction with the result is the fastest way to find out whether you understand the idea or only the words.

Example 3 — an exam-style question

Typical questions about IEC 61000-4-5 ask you to (a) state it precisely, (b) apply it to given data, and (c) explain a limitation. Practise writing all three answers in under five minutes; the third part is what separates a full-mark answer from an average one.

Applications of IEC 61000-4-5

In research
IEC 61000-4-5 appears in physics research whenever the underlying quantities have to be modelled precisely. Papers usually cite it as a starting assumption and then explore where it breaks down.
In technology and industry
Engineering practice reuses IEC 61000-4-5 in design rules, simulations and safety margins. Knowing the idea lets you read a specification sheet and understand why the numbers look the way they do.
In the classroom
IEC 61000-4-5 is common in secondary-school and first-year university syllabi. It links to neighbouring topics Electromagnetic compatibility, IEC standards, so understanding it makes those chapters shorter.
In everyday life
Look for IEC 61000-4-5 outside the textbook — in sport, cooking, traffic, electronics or the sky above you. An example you found yourself is remembered far longer than one you were given.

Affiliate

Preply — study more efficiently by working with a personal tutor. 50% off.

How to study IEC 61000-4-5 in 20 minutes

  1. Read the reference excerpt below once, without taking notes.
  2. Close the page and write down what IEC 61000-4-5 means in your own words.
  3. Compare your version with the excerpt and mark what you missed.
  4. Work through the three examples above with pen and paper.
  5. Explain IEC 61000-4-5 out loud to somebody else — or to Teacher Smith in the lgStudy chat.

Frequently asked questions

What is IEC 61000-4-5 in simple terms?

IEC 61000-4-5 is an international standard by the International Electrotechnical Commission on surge immunity. In an electrical installation, disruptive surges can appear on power and data lines.

Why does IEC 61000-4-5 matter?

Because it connects several physics ideas at once: it gives you a definition you can apply, a quantity you can calculate, and a way to check whether a result is plausible.

How should I study IEC 61000-4-5?

Read the excerpt, restate it from memory, then work through the examples and applications listed on this page. The five-step study plan above takes about twenty minutes.

What does this page cover?

It gives you a compact reference excerpt plus original lgStudy explanations, examples, applications and study material on IEC 61000-4-5.

Tags

  • Electromagnetic compatibility
  • IEC standards

Keep exploring