A residual-current device (RCD), residual-current circuit breaker (RCCB) or ground fault circuit interrupter (GFCI) is an electrical safety device, more specifically a form of earth-leakage circuit breaker, that interrupts an electrical circuit when the current passing through line and neutral conductors of a circuit is not equal (the term residual relating to the imbalance), therefore indicating current leaking to ground, or to an unintended path that bypasses the protective device. The device's purpose is to reduce the severity of injury caused by an electric shock. This type of circuit interrupter cannot protect a person who touches both circuit conductors at the same time, since it then cannot distinguish normal current from that passing through a person. A residual-current circuit breaker with integrated overcurrent protection (RCBO) combines RCD protection with additional overcurrent protection into the same device. These devices are designed to quickly interrupt the protected circuit when it detects that the electric current is unbalanced between the supply and return conductors of the circuit. Any difference between the currents in these conductors indicates leakage current, which presents a shock hazard. Alternating 60 Hz current above 20 mA (0.020 amperes) through the human body is potentially sufficient to cause cardiac arrest or serious harm if it persists for more than a small fraction of a second. RCDs are designed to disconnect the conducting wires ("trip") quickly enough to potentially prevent serious injury to humans, and to prevent damage to electrical devices.
Purpose and operation RCDs are designed to disconnect the circuit if there is a leakage current. In their first implementation in the 1950s, power companies used them to prevent electricity theft where consumers grounded returning circuits rather than connecting them to neutral to inhibit electrical meters from registering their power consumption. The most common modern application is as a safety device to detect small leakage currents (typically 5–30 mA) and disconnecting quickly enough (<30 milliseconds) to prevent device damage or electrocution. They are an essential part of the automatic disconnection of supply (ADS), i.e. to switch off when a fault develops, rather than rely on human intervention, one of the essential tenets of modern electrical practice. To reduce the risk of electrocution, RCDs should operate within 25–40 milliseconds with any leakage currents (through a person) of greater than 30 mA, before electric shock can drive the heart into ventricular fibrillation, the most common cause of death through electric shock. By contrast, conventional circuit breakers or fuses only break the circuit when the total current is excessive (which may be thousands of times the leakage current an RCD responds to). A small leakage current, such as through a person, can be a very serious fault, but does not increase the total current enough for a fuse or overload circuit breaker to isolate the circuit. RCDs operate by measuring the current balance between two conductors using a differential current transformer. This measures the difference between current flowing through line and neutral. If these do not sum to zero, there is a leakage of current to somewhere else (to Earth/ground or to another circuit), and the device will open its contacts. Operation does not require a fault current to return through the earth wire in the installation; the trip will operate just as well if the return path is through plumbing or contact with the ground or anything else. Automatic disconnection and a measure of shock protection is therefore still provided even if the earth wiring of the installation is damaged or incomplete. RCDs are testable and resettable devices—a test button safely creates a small leakage condition, and another button, or switch, resets the conductors after a fault condition has been cleared. Some RCDs disconnect both the line and neutral conductors upon a fault (double pole), while a single pole RCD only disconnects the line conductor. If the fault has left the neutral wire "floating" or not at its expected ground potential for any reason, then a single-pole RCD will leave this conductor still connected to the circuit when it detects the fault. For an RCD used with three-phase power, all three line conductors and the neutral (if fitted) must pass through the current transformer.
Application Electrical plugs with incorporated RCD are sometimes installed on appliances that might be considered to pose a particular safety hazard, for example long extension leads, which might be used outdoors, or garden equipment or hair dryers, which may be used near a bath or basin. Occasionally an in-line RCD may be used to serve a similar function to one in a plug. By putting the RCD in the extension lead, protection is provided at whatever outlet is used even if the building has old wiring, such as knob and tube, or wiring that does not contain a grounding conductor. The in-line RCD can also have a lower tripping threshold than the building to further improve safety for a specific electrical device. In North America, GFI receptacles can be used in cases where there is no grounding conductor, but they must be labeled as "no equipment ground". This is referenced in the National Electric Code section 406 (D) 2; however, codes change and someone should always consult a licensed professional and their local building and safety departments. An ungrounded GFI receptacle will trip using the built-in "test" button, but will not trip using a GFI test plug, because the plug tests by passing a small current from line to the non-existent ground. It is worth noting that despite this, only one GFCI receptacle at the beginning of each circuit is necessary to protect downstream receptacles. There does not appear to be a risk from using multiple GFI receptacles on the same circuit, though it is considered redundant. In Europe, RCDs can fit on the same DIN rail as the miniature circuit breakers; much like in miniature circuit breakers, the busbar arrangements in consumer units and distribution boards provides protection for anything downstream.
… excerpt ends here. Continue reading the full article.